Yaskawa CIMR-UU4A0034A [482/644] B f option settings

Yaskawa CIMR-UU2A0192A [482/644] B f option settings
No.
(Addr.
Hex)
Name LCD Display Description Values Page
F7-18
(03F6)
EtherNet/IP Current
Scaling Factor
EN Current Scale
All Modes
Sets the scaling factor for the output current monitor in
EtherNet/IP Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-19
(03F7)
EtherNet/IP Torque
Scaling Factor
EN Torque Scale
All Modes
Sets the scaling factor for the torque monitor in EtherNet/IP
Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-20
(03F8)
EtherNet/IP Power
Scaling Factor
EN Power Scale
All Modes
Sets the scaling factor for the power monitor in EtherNet/IP
Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-21
(03F9)
EtherNet/IP Voltage
Scaling Factor
EN Voltage Scale
All Modes
Sets the scaling factor for the voltage monitor in EtherNet/IP
Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-22
(03FA)
EtherNet/IP Time
Scaling
EN Time Scale
All Modes
Sets the scaling factor for the time monitor in EtherNet/IP Class
ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-23 to
F7-32
(03FB to
0374)
Dynamic Output
Assembly Parameters
All Modes
Parameters used in Output Assembly 116. Each parameter
contains a MEMOBUS/Modbus address. The value received
for Output Assembly 116 will be written to this corresponding
MEMOBUS/Modbus address. A MEMOBUS/Modbus
address value of 0 means that the value received for Output
Assembly 116 will not be written to any MEMOBUS/Modbus
register.
Default: 0
F7-33 to
F7-42
(0375 to
037E)
Dynamic Input
Assembly Parameters
All Modes
Parameters used in Input Assembly 166. Each parameter
contains a MEMOBUS/Modbus address. The value sent for
Input Assembly 166 will be read from this corresponding
MEMOBUS/Modbus address. A MEMOBUS/Modbus
address value of 0 means that the value sent for Input Assembly
166 is not defined by the user, therefore the option default
register value will be returned.
Default: 0
<1> Cycle power for setting changes to take effect.
<2>
If F7-13 is set to 0, then all IP Addresses (as defined with parameters F7-01 to F7-04) must be unique.