A.5 Drive Derating Data
The drive can
be operated at above the rated temperature, altitude, and default carrier frequency by derating the drive capacity.
u
Rated Current Depending on Carrier Frequency
The table below shows the drive output current depending on the carrier frequency settings.
Use the data in the following tables to linearly calculate output current values for carrier frequencies not listed.
Table A.8
Three-Phase 200 V Class Carrier Frequency and Current Derating
Three-Phase 200 V Class
Drive Model
Rated Current [A]
Normal Duty Rating (ND) Heavy Duty Rating (HD)
4 kHz 6 kHz 8 kHz 10 kHz 4 kHz 6 kHz 8 kHz 10 kHz
2o0028
28 25 22 20 22 20 18 15
2o0042
42 38 34 29 28 25 22 20
2o0054
54 49 43 38 42 38 34 29
2o0068
68 61 54 48 54 49 43 38
2o0081
81 73 65 57 68 61 54 48
2o0104
104 94 83 81 73 65
2o0130
130 117 104 104 94 83
2o0154
154 139 130 117
2o0192
192 173 154 139
2o0248
248 192
Table A.9 Three-Phase 400 V Class Carrier Frequency and Current Derating
Three-Phase 400 V Class
Drive Model
Rated Current [A]
Normal Duty Rating (ND) Heavy Duty Rating (HD)
4 kHz 6 kHz 8 kHz 10 kHz 4 kHz 6 kHz 8 kHz 10 kHz
4o0011
11 9.9 8.8 7.7 9.6 8.6 7.7 6.7
4o0014
14 13 11 9.8 11 9.9 8.8 7.7
4o0021
21 19 17 15 14 13 11 9.8
4o0027
27 24 22 19 21 19 17 15
4o0034
34 31 27 24 27 24 22 19
4o0040
40 36 32 28 34 31 27 24
4o0052
52 47 42 36 40 36 32 28
4o0065
65 59 52 46 52 47 42 36
4o0077
77 69 62 54 65 59 52 46
4o0096
96 86 77 77 69 62
4o0124
124 112 99 96 86 77
4o0156
156 140 124 112
4o0180
180 162 156 140
4o0216
216 180
4o0240
240 216
4o0302
302 240
4o0361
361 302
4o0414
414 361
u
Carrier Frequency Derating
Derate the drive according to Figure A.1 as the carrier frequency increases above the factory default setting.
A.5 Drive Derating Data
438
YASKAWA ELECTRIC SIEP C710636 04C U1000 Industrial MATRIX Drive Technical Manual