Yaskawa CIMR-UU4A0034A [454/644] B8 energy saving

Yaskawa CIMR-UU4A0216A [454/644] B8 energy saving
u
b8: Energy Saving
No.
(Addr.
Hex)
Name LCD Display Description Values Page
b8-01
(01CC)
Energy Saving Control
Selection
Energy Save Sel
0: Disabled
1: Enabled
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
0: Disabled
1: Enabled
Default:
<1>
Range: 0, 1
188
b8-02
(01CD)
Energy Saving Gain Energy Save Gain
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVOLV CLV
Sets the gain used for Energy Saving.
Default:
<1>
Min.: 0.0
Max.: 10.0
188
b8-03
(01CE)
Energy Saving Control
Filter Time Constant
Energy Save F.T
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVOLV CLV
Sets a time constant for Energy Saving.
Default:
<2>
Min.: 0.00 s
Max.: 10.00 s
189
b8-04
(01CF)
Energy Saving
Coefficient Value
Energy Save COEF
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f V/f w PG
Determines the level of maximum motor efficiency. Setting
range is 0.0 to 2000.0 for drives 3.7 kW and smaller. The display
resolution depends on the rated output current after the Drive
Duty has been set in parameter C6-01. Refer to Model Number
and Nameplate Check on page 34.
Default:
<3> <4>
Min.: 0.00
Max.: 655.00
189
b8-05
(01D0)
Power Detection Filter
Time
kW Filter Time
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f V/f w PG
Sets a time constant filter for output power detection.
Default: 20 ms
Min.: 0
Max.: 2000
189
b8-06
(01D1)
Search Operation
Voltage Limit
Search V Limit
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f V/f w PG
Sets the limit for the voltage search operation as a percentage
of the motor rated voltage.
Default: 0%
Min.: 0
Max.: 100
189
b8-16
(01F8)
Energy Saving
Parameter (Ki) for PM
Motors
PM Enrgy Save Ki
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
OLV/PM AOLV/PM CLV/PMOLV/PM AOLV/PM CLV/PM
V/fOLV/PM
Coefficient to adjust torque linearity.
Set to the Ki value on the motor nameplate.
When parameter E5-01, Motor Code Selection (for PM
Motors), is set to 1ooo or 2ooo, the automatically
calculated value will be set. This set value cannot be changed.
Default: 1.00
Min.: 0.00
Max.: 3.00
189
b8-17
(01F9)
Energy Saving
Parameter (Kt) for PM
Motors
PM Enrgy Save Kt
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
OLV/PM AOLV/PM CLV/PMOLV/PM AOLV/PM CLV/PM
V/fOLV/PM
Coefficient to adjust torque linearity.
Set to the Kt value on the motor nameplate.
When parameter E5-01, Motor Code Selection (for PM
Motors), is set to 1ooo or 2ooo, the automatically
calculated value will be set. This set value cannot be changed.
Default: 1.00
Min.: 0.00
Max.: 3.00
189
<1> Default setting is determined by parameter A1-02, Control Method Selection.
<2> Default setting is determined by parameters A1-02, Control Method Selection, and o2-04, Drive Model Selection.
<3> Default setting is determined by parameters o2-04, Drive Model Selection, and C6-01, Drive Duty Selection.
<4>
Parameter value changes automatically if E2-11 is manually changed or changed by Auto-Tuning.
u
b9: Zero Servo
No.
(Addr.
Hex)
Name LCD Display Description Values Page
b9-01
(01DA)
Zero Servo Gain Zero Servo Gain
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
Sets the position loop gain for the Zero Servo function.
Default: 5
Min.: 0
Max.: 100
190
b9-02
(01DB)
Zero Servo Completion
Width
Zero Servo Count
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
Sets the range to trigger an output terminal set for “Zero Servo
Complete” during Zero Servo operation.
Default: 10
Min.: 0
Max.: 16383
190