Daikin EUWAC10FZW [122/264] Thermostat control euwac5 10fzw1

Daikin EUWAC5FZW [122/264] Thermostat control euwac5 10fzw1
ESIE-0302 Functional Description
Part 2 – Functional Description 2–11
3
2
4
5
1
1.8 Thermostat Control: EUWAC5-10FZW1
Thermostat control The illustration below shows the thermostat control of EUWAC5-8-10FZW1.
Controller The table below describes the step difference.
12
ON
r1: Cooling set point
(default 12°C)
OFF
Compressor
15
Inlet water temperature
evap. (°C)
Step
difference
r1
r2
Description Lower limit Upper limit Step Default
r2: Step difference (°C) 0.3 19.9 0.1 3.0