Daikin EUWAC10FZW [18/264] The table below contains the minimum water volume settings

Daikin EUWAC5FZW [18/264] The table below contains the minimum water volume settings
ESIE-0302 General Outline
Part 1 – System Outline 1–9
3
1
4
5
(1)
: The table below contains the minimum water volume settings.
Oil charge volume 1.5 l 2.7 l
No. of circuits 1
Pump
No. x type __ 1 x Horizontal multi-stage end-suction __ 1 x Horizontal multi-stage end-suction
Model __ CH4-30 CH4-30
Nominal static
height pump
__ 238 kPa 216 kPa
Nominal static
height unit
__ 205 kPa 154 kPa
Hydraulic components
Buffer tank __ 55 l __ 55 l
Unit water volume 2 l 3 l 59 l 3 l 3 l 59 l
Expansion vessel __ 12 l __ 12 l
Pre-pressure
expansion vessel
1.5 bar 1.5 bar
Safety valve __ 3 bar __ 3 bar
Dimensions
(h x w x d)
1230 x 1290 x 734 mm 1230 x 1290 x 734 mm
Weight
Machine weight 150 kg 168 kg 180 kg 215 kg 229 kg 241 kg
Operation weight 152 kg 171 kg 239 kg 218 kg 232 kg 300 kg
Casing
Colour Ivory white / Munsell code 5Y7.5/1 / ± RAL 7044
Material Polyester coated galvanised steel plate
Sound power
level
(2)
67 dBA 76 dBA
Safety devices
Low-pressure switch
High-pressure switch
Pump motor overcurrent
Discharge temperature control
Outlet water temperature protection
Compressor motor overcurrent relay
Fan thermal protector
Anti-recycling and guard timer
Digital display controller with electronic temperature control
Reverse phase protector
Flow switch.
Model EUWAN5KZW1 EUWAP5KZW1 EUWAB5KZW1 EUWAN8KZW1 EUWAP8KZW1 EUWAB8KZW1
Setting EUWA5-12KZW1
The minimum water volume for standard thermostat difference setting 3 K
For reduced setting multiply this water volume by 3/new setting
Minimum allowable setting 0.1 K