Daikin EUWAC10FZW [53/264] Electrical specifications euwy 5 8kzw1

Daikin EUWAC5FZW [53/264] Electrical specifications euwy 5 8kzw1
General Outline ESIE-0302
1–44 Part 1 – System Outline
3
1
1
4
5
1.17 Electrical Specifications: EUWY*5-8KZW1
Electrical
specifications
The table below contains the electrical specifications
(1)
.
Model EUWYN5KZW1 EUWYP5KZW1 EUWYB5KZW1 EUWYN8KZW1 EUWYP8KZW1 EUWYB8KZW1
Power supply
Phase 3N~
Frequency 50 Hz
Voltage 400 V
Voltage tolerance ± 10 %
Unit
Starting current 62.2 A 63.5 A 97.9 A 99.2 A
Nominal running
current cooling
7.7 A 9.0 A 13.6 A 14.9 A
Max. running
current
11.2 A 12.5 A 16.9 A 18.2 A
Recommended
fuses
3 x 20 gL/gG 3 x 20 gL/gG 3 x 25 gL/gG 3 x 25 gL/gG
Fans
Phase 1~
Voltage 230 V
Max. running
current
2.2 A 2.9 A
Compressor
Phase 3~
Voltage 400 V
Starting current
60.0 A 95.0 A
Nom. running
current cooling
5.5 A 10.7 A
Max. running
current
9.0 A 14.0 A
Starting method Direct on line
Control circuit
Phase 1~
Voltage 230 V
Recommended
fuses
Factory installed
Pump
Phase__3~__3~
Voltage __ 400.0 V __ 400.0 V
Max. running
current
__ 1.3 A __ 1.3 A

Содержание

Скачать