1.17 Freeze-up Control: EUWAC5-10FZW1
Functional
description
The freeze-up control is a protection against ice formation in the water circuit at the evaporator outlet.
Characteristics The table below contains the characteristics of the freeze-up protection.
Characteristics for
glycol option
The table below contains the characteristics of the freeze-up protection for glycol option.
Characteristics Freeze-up protection
Control device Sensor
Diagram name R4T
Activation Outlet water temperature. < 2.5°C
Result: The circuit is disabled.
Reset Manually on the controller if temperature > 7.5°C
(2.5°C + anti-freeze hysteresis).
Result: The circuit restarts.
ZL Activation Outlet water temperature < -11.5°C
Reset Manually on controller if temperature > -6.5°C
(-11.5°C + anti-freeze hysteresis).
ZH Activation Outlet water temperature < -6.5°C
Reset Manually on the controller if temperature > -1.5°C
(-6.5°C + anti-freeze hysteresis).