Daikin EUWAC10FZW [36/264] The table below contains the minimum water volume settings

Daikin EUWAC5FZW [36/264] The table below contains the minimum water volume settings
ESIE-0302 General Outline
Part 1 – System Outline 1–27
3
1
4
5
(1)
: The table below contains the minimum water volume settings.
Oil charge volume 2 x 2.7 l
No. of circuits 2
Pump
No. x type __ 1 x Horizontal multi-stage end-suction __ 1 x Horizontal multi-stage end-suction
Model __ CH8-30 __ CH8-30
Nominal static
height pump
__ Cooling: 251 kPa
Heating: 243 kPa
__ Cooling: 227 kPa
Heating: 204 kPa
Nominal static
height unit
__ Cooling: 209 kPa
Heating: 195 kPa
__ Cooling: 171 kPa
Heating: 134 kPa
Hydraulic components
Buffer tank __ 55 l __ 55 l
Unit water volume 6 l 9 l 65 l 6 l 10 l 66 l
Expansion vessel __ 12 l __ 12 l
Pre-pressure
expansion vessel
1.5 bar
Safety valve __ 3 bar __ 3 bar
Dimensions
(h x w x d)
1321 x 2580 x 734 mm 1541 x 2580 x 734 mm
Weight
Machine weight 455 kg 473 kg 485 kg 516 kg 534 kg 546 kg
Operation weight 461 kg 482 kg 550 kg 522 kg 544 kg 612 kg
Casing
Colour Ivory white / Munsell code 5Y7.5/1 / ± RAL 7044
Material Polyester coated galvanised steel plate
Sound power
level
(2)
79 dBA 81 dBA
Safety devices
Low-pressure switch
High-pressure switch
Pump motor overcurrent
Discharge temperature protection
Outlet water temperature protection
Compressor motor overcurrent relay
Fan thermal protector
Anti-recycling and guard timer
Digital display controller with electronic temperature control
Reverse phase protector
Flow switch.
Model EUWYN16KZW1 EUWYP16KZW1 EUWYB16KZW1 EUWYN20KZW1 EUWYP20KZW1 EUWYB20KZW1
Setting EUWY*16-20KZW1
The minimum water volume for standard thermostat difference setting 3 K
For reduced setting multiply this water volume by 3/new setting
Minimum allowable setting 0.1 K