Daikin EUWAC10FZW [175/264] Checking the power supply and fuses euwa 5 24kzw1 and euwy 5 24kzw1

Daikin EUWAC5FZW [175/264] Checking the power supply and fuses euwa 5 24kzw1 and euwy 5 24kzw1
Checking the Inputs and Outputs ESIE-0302
3–24 Part 3 – Troubleshooting
3
1
3
4
5
3.8 Checking the Power Supply and Fuses: EUWA*5-24KZW1 and EUWY*5-24KZW1
Overview The table below contains an overview of the circuits, the voltage and their fuse codes.
Overview fuses and
overcurrent
The table below contains an overview of the fuses and overcurrent for types EUWA*5-24KZW1 and
EUWY*5-24KZW1.
Circuit Wiring code Type / voltage Fuse code
Main supply L1 + L2 + L3 + N 3 phases / 400 V AC F1+F2+F3
Control circuit I/O PCB L1 + N
L3 + N
1 phase / 230 V AC
1 phase / 230 V AC
F4
F1U
Control circuit controller TR1-sec. 24 V AC F3U, F5U
Control circuit (pump) for
EUWAN5-24KZW1
X1M 8-7 24 V AC F6
Fan circuit for
EUWA*5-12KZW1
L1 + N 1 phase / 230 V AC F7
Fan circuit for
EUWA*18-24KZW1
L1 + N 1 phase / 230 V AC F8
All models (400 V)
Fuses +
overcurrent
5HP 8HP 10HP 12HP 16HP 20HP 24HP
F4 8 A 8 A 8 A 8 A 8 A 8 A 8 A
F5 125 mAT 125 mAT 125 mAT 125 mAT 125 mAT 125 mAT 125 mAT
F7, F8 5 A 5 A 5 A 5 A 5 A 5 A 5 A
F1U 5 A 5 A 5 A 5 A5 A5 A5 A
F3U 315 mAT 315 mAT 315 mAT 315 mAT 315 mAT 315 mAT 315 mAT
K4S 9 A 13 A 16 A 24 A 13 A 16 A 24 A
K5S ___ ___ ___ ___ 13 A 16 A 24 A
K6S
(st. pump)
1.4 A 1.4 A 1.4 A 1.4 A 2 A 2 A 2 A
K6S
(op. pump
high)
2 A 2 A 2 A 2 A 3.7 A 3.7 A 3.7 A
Units with integrated pump
Fuses 5HP 8HP 10HP 12HP 16HP 20HP 24HP
F1, F2, F3
(=gL/gG)
3 X 20 A 3 X 25 A 3 X 32 A 3 X 40 A 3 X 50 A 3 X 50 A 3 X 63 A
Units without integrated pump
Fuses 5HP 8HP 10HP 12HP 16HP 20HP 24HP
F1, F2, F3
(=gL/gG)
3 X 20 A 3 X 25 A 3 X 25 A 3 X 32 A 3 X 40 A 3 X 50 A 3 X 63 A