Troubleshooting ESIE-0302
3–48 Part 3 – Troubleshooting
3
1
3
4
5
Anti-freeze and
supporting heaters
The table below contains the settings of the anti-freeze and the supporting heaters.
Alarm The table below contains the settings of the alarm.
dv Factory Delay before defrosting 0 min r/w
dd Factory Delay after defrosting 0 min
Code Parameter Function EUWY*5-24KZW1
Read/
write
Code Parameter Function
EUWY*5-
12KZW1
EUWY*16-
24KZW1
Read/
write
a1 Direct Anti-freeze alarm set
point
Standard 4˚C 4˚C r/w
ZL option -11.5˚C -11.5˚C
ZH option -6.5˚C -6.5˚C
a2 Direct Anti-freeze alarm hysteresis 3.5˚C 3.5˚C
a3 Direct Bypass time for anti-freeze alarm 0 s 0 s
a4 Direct Anti-freeze heater set
point
Standard 4˚C 4˚C
ZL option -10˚C -10˚C
ZH option -5˚C -5˚C
a5 Factory Anti-freeze heater hysteresis 3˚C 3˚C
a6 Factory Supporting heaters probe 0 0
a7 Factory Limit anti-freeze alarm set -15˚C -15˚C
a8 Factory Set point for the supporting heater 25˚C 25˚C
a9 Factory Heating support resistance diff. 3˚C 3˚C
aa Factory Automatic switch-on for anti-frost 0˚C 0˚C
Code Parameter Function
EUWY*5-
12KZW1
EUWY*16-
24KZW1
Read/
write
p1 Factory Flow-start timer 20 s 20 s r/w
p2 Factory Flow-stop timer 5 s 5 s
p3 Factory LP bypass timer 60 s 60 s
p4 User Buzzer ON time 1 min 1 min
p5 Factory Reset of alarms 0 0
p8 Factory Selection of digital input ID1 1 1
p9 Factory Selection of digital input ID2 8 8
pa Factory LP alarm when the compr. is OFF 0 0
pb Factory High temp. alarm set 90˚C 90˚C
pv Factory High temp. alarm delayed at
start-up
30 min 30 min r/w