Daikin EWAD650BJYNN/Q [144/346] Operational range ewad bjynn

Daikin EWADC14BJYNN [144/346] Operational range ewad bjynn
Operation Range ESIE 07-04
2–4 Part 2 – Functional Description
3
1
2
4
5
1.2 Operational Range: EWAD-BJYNN
Operational range The illustration below shows the operational range of EWAD-BJYNN.
Notes (1) When air temperature is lower than +10°C, the fan speed control device (OPFS) should be used.
It allows the unit to work with air temperature down to -10°C. Low ambient operation (OPLA) allows to
reach -18°C.
-30
-20
0
-10
10
20
40
50
Ambient C
Leaving
evaporator
water
temperature
C
-20 -10 0 10 20 30
standard unit
with Fanspeed control
device : OPFS
with Low ambient
operation : OPLA
water
94-8
-18
44
glycol
Unit version EWAD-BJYNN
Max ambient temperature +44°C
Min ambient temperature +10°C (1)
Max leaving evaporator water temperature +9°C
Min leaving evaporator water temperature (without glycol) +4°C
Min leaving evaporator water temperature (with glycol) -8°C
Max evaporator T8°C
Min evaporator T4°C