Daikin EWAD650BJYNN/Q [175/346] Autorestart after

Daikin EWADC14BJYNN [175/346] Autorestart after
ESIE07-04 The Digital Controller
Part 2 – Functional Description 2–35
3
2
4
5
1
Pump lead time This screen allows you to set the time between the main pump and the compressor start.
Pump lag time This screen allows you to set the delay on switching off the pump.
Supervisory remote This screen allows you to enable/disable supervisory remote on/off function.
Auto restart This screen allows you to enable/disable the auto restart after power failure.
P Time 30s : Pump lead time, the pump will operate for 30 seconds (changeable) before the
compressor can start
Pump / Fan and Comp.
Start
030 s
Time Between Main
P Delay 180 s : Pump lag time, the pump will operate for another 180 seconds (changeable)
when the unit is requested to shut down (local / remote / thermostat)
the Main Pump Off
180 s
Delay on Switching
P N : The unit will be controlled on/off by local/remote switch/keypad
P Y : Allows supervisor or BMS to control the on/off function of the unit
Supervisory Remote
On / Off N
P N : After a power failure, the unit will not automatically restart
P Y : After a power failure, the unit will automatically restart
Power Failure Y
Autorestart After