Daikin EWAD650BJYNN/Q [168/346] Demand limit xx

Daikin EWADC11BJYNN [168/346] Demand limit xx
The Digital Controller ESIE07-04
2–28 Part 2 – Functional Description
3
1
2
4
5
Line 4 gives the setpoint origin :
Unit limiting This screen is only visible when unit limiting (demand limit) is enabled in the user menu.
Water temperatures This screen shows the water temperatures.
P STP Source : Local
: Double
: 4-20 mA
P Soft Load : xx min (remaining soft load time)
P Demand Limit : Read-out of the selected capacity limitation according to the supplied
4-20 mA signal.
Unit Limiting
Demand Limit xx%
P ENT Evap : Entering water temperature
P LVG Evap : Leaving water temperature (common leaving water if 2 evaps. are present)
Water Temperatures
ENT Evap = 00.0˚C
LVG Evap = 00.0˚C