Daikin EWAD650BJYNN/Q [295/346] Configuration procedure for the plan settings

Daikin EWAD700BJYNN [295/346] Configuration procedure for the plan settings
ESIE07-04 Procedure for the Changing and Configuration of the Display
Part 3 – Troubleshooting 3–39
33
4
5
1
6.3 Configuration Procedure for the pLan Settings
This procedure must be done in case a terminal is replaced or added (remote controller) in the pLan
or if settings are changed.
To start configuration, proceed as follows:
Step Action Result
1 Turn on the power supply Nothing will appear on the screen
because no configuration has been made.
2
Hold down , and simulta-
neously for five seconds.
A screen will appear with the terminal
address and with the address of the board
in examination:
Using the “up” and “down” keys it is possi-
ble to choose the different boards (1 and 2
for pCO² controller and 3, 4, 5 and 6 for
the electronic valve drivers.
3 Select in correspondence with “I/O Board
Addr” the number 1 (Board with address
1) and push “enter”.
In about two seconds the following screen
will appear:
4 Push “enter” again. The following screen will appear:will
appear:
5 If you want to add a second terminal
(remote terminal), change the line “Trm2
None-” with the line “Trm2 8 Sh’
The following screen will be displayed on
the screen:
6 To enable the new configuration put the
pointer on “No” (using the key “enter” and
with “up” and “down” change it to “Yes”
and push enter.
The new configuration is enabled.
Remarks:
P The operations from 1 to 4 must be
repeated for all compressor boards
(“I/O Board” 1 and 2).
P The operations from 1 to 5 must be
repeated for all compressor boards
(“I/O Board” 1 and 2) if remote terminal
is connected.
enter
Terminal Addr: 7
I/O Board Addr: n
Press ENTER
To continue
Terminal Config
P: 01
Tr m2
Tr m1
Tr m3
Addr
None
7
None
Priv/Shared
---
Sh
---Ok? No
P: 01
Tr m2
Tr m1
Tr m3
Addr
8
7
None
Priv/Shared
Sch
Sh
---Ok? No