Daikin EWAD650BJYNN/Q [146/346] Operational range ewad bjynn q

Daikin EWADC14BJYNN [146/346] Operational range ewad bjynn q
Operation Range ESIE 07-04
2–6 Part 2 – Functional Description
3
1
2
4
5
1.4 Operational Range: EWAD-BJYNN/Q
Operational range The illustration below shows the operational range of EWAD-BJYNN/Q.
Notes (1) When air temperature is higher than +32°C, the fan speed control device (standard on /Q units)
sets up speed rotation increasing cooling capacity and sound pressure level.
(2) Fan speed control device (OPFS) is standard equipment on the /Q units.
-30
-20
0
-10
10
20
40
50
-20 -10 0 10 20 30
Ambient C
Leaving
evaporator
water
temperature
C
water
94-8
-18
glycol
Unit version EWAD-BJYNN
Max ambient temperature +40°C (1)
Min ambient temperature -10°C (2)
Max leaving evaporator water temperature +9°C
Min leaving evaporator water temperature (without glycol) +4°C
Min leaving evaporator water temperature (with glycol) -8°C
Max evaporator T8°C
Min evaporator T4°C