Daikin EWAD650BJYNN/Q [247/346] Lp alarm delay

Daikin EWAD650BJYNN/Q [247/346] Lp alarm delay
ESIE07-04 Functional Control
Part 2 – Functional Description 2–107
3
2
4
5
1
3.23 LP alarm delay
Function
description
Delay timer before the unit goes into LP alarm.
P start delay: At start up the unit has a delay of 120 seconds before the unit can trip on LP alarm (low
pressure bypass timer)
P run delay: When the unit is in operation, the low pressure can be below the LP alarm setpoint for
a specified time before the unit will trip on LP alarm.
Low Press. Alarm Delays
Start-Up Delay :
Run Delay :
060 s
040 s