ESIE07-04 The Digital Controller
Part 2 – Functional Description 2–29
3
2
4
5
1
Compressor status This screen shows the compressor status.
Refrigerant
pressures
This screen shows the high and low pressure of this circuit.
Possible status :
P Off Alarm : Compressor OFF for alarm
P Off Switch : Compressor OFF by local switch
P Off Ready : Compressor OFF ready to start
P Oil Heating : Compressor waiting for oil heating
P Manual Off : Compressor disabled by keypad
P Recycle Time : Compressor waiting for timing
P Starting : Compressor starting
P Pre Purge : Compressor unloading at starting
P Auto xx% : Automatic control of compressor with percent load
P Manual xx% : Manual control of compressor with percent load
P Downl. : Compressor download before stop
P Pumping down : Compressor pump down
Comp. # 01
Status : Off Ready
P Evap Press : Evaporating Pressure
P Evap Temp : Evaporating Temperature
P Cond Press : Condensing Pressure
P Cond Temp : Condensing Temperature
Evap Press = 00.0 bar g
Evap Temp = 00.0 ˚C
Cond Press = 00.0 bar g
Cond Temp = 00.0 ˚C