ESIE07-04 Functional Control
Part 2 – Functional Description 2–79
3
2
4
5
1
Loading and
unloading zones
The graph below shows the different loading and unloading zones.
Settings Do not change:
P Max pull down : 0.7° / min
P Dead band : 0.2°C
P Reload T : 0.7°C
P Interstage : 210 s
18a (T in load
band)
Load up to 75% Stop Off Off
18b (T not in load
band)
Fixed at 50% Stop Off Off
19 Unload up to 25% Off Off Off
20 If T is approaching SetP – Waiting
21 If (SetP – T) < Shutdown DT & Cooling
or (T – SetP) < Shutdown DT & Heating
Waiting
22 Stop Off Off Off
23 Off Off Off Off
Step n. Leader Comp. Lag 1 Comp. Lag 2 Comp. Lag 3 Comp.
loading
band
unloading
band
dead band
0.2 C
reload T
0.7 C
reload T
0.7 C
start up T : 2.7 Cshut down T : 1.7 C
Regulation band : 3 C
5.3 5.5 6.3 7
7.7
8.5 9.7
123
4a4b