Daikin EWAD850BJYNN/A [233/346] Liquid injection

Daikin EWAD850BJYNN/A [233/346] Liquid injection
ESIE07-04 Functional Control
Part 2 – Functional Description 2–93
3
2
4
5
1
3.13 Liquid Injection
Function
description
P When the oil temperature (PT1000; del. temp.) is higher than 85°C (default) the liquid injection will
be activated.
P When the oil temperature decreases to 75% the loquid injection will be disabled.
Liq. Inj. OFF
Liq. Inj. ON
(del Temp.) Oil Temp.
75 C 85 C
Setpoint
Diff.
085 ˚C
10.0 ˚C
Liquid Injection