Procedure for the Changing and Configuration of the Display ESIE07-04
3–40 Part 3 – Troubleshooting
3
1
3
4
5
Remark:
It is possible after restart that the terminal is stuck in a unit. This is due to the fact that the memory of
the drivers remains fed by the buffer battery and keeps on processing the data contained in the
preceding configuration. In this case, with the system not fed, it is sufficient to disconnect batteries
from all the drivers and then connect them again.
7 At the end of the operations turn off and
restart the system.
Step Action Result