Daikin EUWA(*)100JX [110/145] Items to be checked

Daikin EUWA(*)100JX [110/145] Items to be checked
Troubleshooting ESIE97–02
3–22 Part 3 – Troubleshooting
4.2 Items to Be Checked
Introduction In the tables below the most frequent failures and their corrective action are explained. Use these
tables when the unit or a circuit does not start.
No malfunction
indication
The unit does not start and there is no malfunction indication.
Malfunction
indication
The unit does not start because of a malfunction.
Possible causes Items to be checked
Power supply problem
Main supply
Control system supply
Pcb supply
Loose or broken connections
Blown fuses (due to short circuit)
Defective transformer
The unit is not switched on
Check the remote start/stop setup and correct if setup
incorrectly
Check the field wiring in case of remote control
One of the timers is still active Check the timers overview in this manual or in the controller
and wait until all timers have elapsed
The unit is programmed incorrectly. Check the settings.
The compressor step in manual mode control should
not be set to 0%.
Problem Possible causes Items to be checked
Freeze-up
Water flow too low
Refrigerant shortage
Operation out of range
Defective thermostat control
Pump operation
Water flow (closed valves and blocked
circuits)
Flow switch operation
Operation condition
Blocked parts in the refrigerant system
Refrigerant leaks
Overcurrent in
the compressor
Failure on one of the phases
Low supply voltage
Motor overload
Power supply
Fuses
Mains isolator switch
Mains relay contacts
Operation condition
Compressor windings
Current on all 3 phases
Reset the overcurrent relay

Содержание

Скачать