ESIE97–02 Functional Control
Part 2 – Functional Description 2–17
1.10 Head Pressure Setback
Introduction The following table explains wen a high pressure (HP) setback can occur:
Reset Once activated, the head pressure setback will stop after 3 minutes.
If... and... then...
HP >15.5 bar (59°C) compressor step=100% compressor step becomes 70%.