Daikin EUWA(*)100JX [16/145] Electrical specifications

Daikin EUWA(*)100JX [16/145] Electrical specifications
General Outline ESIE97–02
1–8 Part 1 – System Outline
1.3 Electrical specifications
EUWA(*)40-60JX In the following table you will find the electrical specifications of chiller types EUWA(*)40-60JX
(1)
: Nominal conditions are as follows:
entering/leaving water temperature 12/7 °C
ambient air temperature 35 °C
input includes total input of the unit:
compressor + fan motor + control circuit + pumps
Model EUWA(*)40JX EUWA(*)50JX EUWA(*)60JX
Power supply Y1 Y1 Y1
Compressor
phase
starting current
max. running current
starting method
voltage
nominal running current
3~
126 A
86.5 A
star-delta
400 V
59 A
3~
181 A
111 A
star-delta
400 V
84 A
3~
181 A
133 A
star-delta
400 V
98 A
Nominal distribution system voltage
phase
frequency
voltage
voltage tolerance
3~
50 Hz
400 V
±10 V
3~
50 Hz
400 V
±10 V
3~
50 Hz
400 V
±10 V
Control circuit
phase
recommended fuses
voltage
1~
factory installed
230 V
1~
factory installed
230 V
1~
factory installed
230 V
Unit
nominal running current
(1)
starting current
recommended fuses
max. running current
68.5 A
126 A
3x125aM
96 A
96 A
181 A
3 x 160 aM
123 A
110 A
181 A
3x160aM
145 A