MEAN WELL MPT-65A [34/112] Din series

MEAN WELL MFM-10-15 [34/112] Din series
31
DIN Series
480~960W Slim 3-phase High Input Voltage
Model No. Output Tol. R&N Effi.
TDR-480-24 24V, 0~20A ±1.0% 150mV 92.5%
TDR-480-48 48V, 0~10A ±1.0% 150mV 93%
Model No. Output Tol. R&N Effi.
TDR-960-24 24V, 0~40A ±1.0% 180mV 94.0%
TDR-960-48 48V, 0~20A ±1.0% 250mV 94.5%
TDR-960
TDR-480
General Specification (Please refer to www.meanwell.com for detail spec.)
Model No. TDR-480 TDR-960
AC input voltage range 3-phase 340~550VAC (2-phase operation possible), 480~780VDC
AC input current (Typ.) 0.85A / 400VAC, 0.7A / 500VAC 2.0A / 400VAC, 1.4A / 500VAC
AC inrush current (max.) Cold start, 50A at 400VAC Cold start, 60A at 400VAC
DC adjustment range 24V: 24~28V, 48V: 48~55V
Overload protection 105%~130% rated output power, constant current limiting, unit will shut down after 3 sec., re-power on to recover
Over voltage
protection
Range 29~33V for 24V model, 56~65V for 48V model
Type Shut down o/p voltage, re-power on to recover
Over temperature protection Shut down o/p voltage, auto-recovery after temperature goes down
Withstand voltage I/P-O/P:3kVAC I/P-FG:2kVAC O/P-FG:0.5kVAC, O/P-DC OK: 0.5kVAC(TDR-960; optional for TDR-480)
Working temperature -30~+70°C (refer to output derating curve)
Safety standards
UL508 approved
EMC standards EN55032 class B, EN55032 class B(TDR-480 only), EN61000-3-2,3, EN61000-4-2,3,4,5,6,8,11, EN61204-3, heavy industry level
Connection
(screw DIN terminal)
I/P: 4 poles, O/P: 4 poles I/P: 4 poles, O/P: 6 poles
Case No. 984E 214A
Dimension (WxHxD)(mm) 85.5x 125.2x 128.5 110x 125.2x 150
480W TDR-480
960W TDR-960
Features
• 3-phase, 340~550VAC wide range input
(2-phase operation possible)
• Width only 110mm for TDR-960; 85.5mm for TDR-480
Built-in active PFC function
• High efficiency up to 94.5%
• Protections: Short circuit / Overload / Over voltage /
Over temperature
• Cooling by free air convection
• DC output voltage adjustable
• Built-in constant current limiting circuit
• Can be installed on DIN rail TS-35/7.5 or 15
• UL508(industrial control equipment)approved
• EN61000-6-2(EN50082-2) industrial immunity level
• Current sharing up to 3840W(3+1) for TDR-960
• Built-in DC OK relay contact (optional for TDR-480)
• 3 years warranty
(TDR-960 only)
3-phase, 340~550VAC wide range input
Built-in active PFC function
• High efficiency up to 93%
Protections:
Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Built-in constant current limiting circuit
Can be installed on DIN rail TS-35/7.5 or 15
Design refer to UL508
Output models: 24V / 48V
Dimension(WxHxD): 63x 125.2x 113.5mm
3 years warranty