Daikin FH35BZV1 [26/26] Safety device settings

Daikin FH35BZV1 [26/26] Safety device settings
9
Safety device settings
FHY-GZ
Model Safety devices 35 45
FHY-GZ
Fuse −−
Fan motor thermal fuse (°C) −−
Fan motor thermal protector (°C)
Off: 130±5
On: 83±20
Off: 130±5
On: 83±20
3TW21009-2A
Model Safety devices 35 50 60 71 100 125
FHYP-BV1
Fuse −−−−−−
Fan motor thermal fuse (°C) −−−−−−
Fan motor thermal protector (°C)
OFF: 130±5
ON: 83±20
OFF: 130±5
ON: 83±20
OFF: 130±5
ON: 83±20
OFF: 130±5
ON: 83±20
OFF: 130±5
ON: 83±20
OFF: 130±5
ON: 83±20
FH-BZV1
Fuse 250V 5A 250V 5A 250V 5A 250V 5A 250V 5A 250V 5A
Fan motor thermal fuse (°C) −−−−−−
Fan motor thermal protector (°C)
OFF: 130±5
ON: 83±20
OFF: 130±5
ON: 83±20
OFF: 130±5
ON: 83±20
OFF: 130±5
ON: 83±20
OFF: 130±5
ON: 83±20
OFF: 130±5
ON: 83±20
3D006611C
10 Installation
Names and functions of parts
j
a
Indoor unit
j
b
Outdoor unit
j
c
Remote control
j
d
Inlet air
j
e
Discharged air
j
f
Air outlet
j
g
Blade (at air outlet)
j
h
Refrigerant piping, connection electric wire
j
i
Drain pipe
j
j
Air inlet
The built-in air filter removes dust and dirt.
j
k
Ground wire
Wire to ground from the outdoor unit to prevent electrical
shocks.
Ceiling Suspended Unit R-407C FH(Y)-GZ/BZ/FHYP-B
10
9
24
Split - Sky Air Indoor Units

Содержание

Скачать