Daikin CDK25AZVMB [24/62] Comfortable

Daikin 4MK58AZVMB [24/62] Comfortable
23
SPECIFICATIONS
Power supply
Cooling capacity/ kW
Max. cooling capacity Btu/h
kcal/h
Heating capacity/ kW
Max. heating capacity Btu/h
kcal/h
Average COP of Cool/Heat
Dimensions (HxWxD) mm
Weight kg
Max. ref. piping length m
Charged for m
Operation sound (C/H) dBA
Night quiet mode dBA
MFA( ) for FDYP (Australia) A
Operation range cooling °CDB
heating °CWB
RZP71DV1 RZP100DV1 RZP125DV1
1 phase, 220-240V, 50Hz
6.9(3.2-7.8) 9.7(4.9-11.0) 12.1(5.8-13.8)
23,600 33,100 41,300
(10,900-26,600) (16,700-37,600) (19,800-47,100)
5,900(2,800-6,700) 8,300(4,200-9,500) 10,400(5,000-11,900)
7.8(3.4-8.8) 11.0(5.5-12.6) 13.7(5.9-15.9)
26,600 37,600 46,800
(11,600-30,000) (18,800-43,100) (20,100-54,300)
6,700(2,900-7,600) 9,500(4,700-10,800) 11,800(5,100-13,700)
TBC TBC TBC
905x900x320 1,435x900x320 1,435x900x320
71 119 119
50 70 70
30 30 30
48/50 50/52 51/53
45 45 45
20 30(41) 30(40)
-5~50 -5~50 -5~50
-15~16 -15~16 -15~16
COMFORTABLE
1. Comfortable control by inverter
During start up, full power is used to achieve the room set point temperature quickly.
The capacity is then adjusted according to the outdoor temperature and indoor load varations
to achieve fine control of the room temperature setting. Non inverter type air conditioners
switch on and off repeatedly, causing large fluctuations in room temperature.
2. Reduced sound level via:
Hybrid aerofoil fan - Super aero grille
(explanation cf “Smooth air flow mechanism”)
Low-noise compressor
Smooth rotation and minimal vibrations ensure quiet operation
Night quiet mode
Reduces normal operating noise level by trimming compressor and fan rotation rate during
low load night time operation.
3. Expansion of the operation range
- Heating operation ranges down to -15°CWB
- Cooling operation ranges up to 50°CDB
4. Maximum piping length up till 70m (for 100 & 125 model)