52
17 pCO
2
CONTROLLER
BACKGROUND
To respond to the increasing market demand for accurate control, all Daikin chillers will be equipped
with the newest pCO
2
controller.
FUNCTIONS
Advanced pCO
2
DDC controller offering following functions:
Schedule timer: Four timer groups can be used, in which up to nine time related actions can be
defined. Days appointed to a timer group will follow the time related action settings of that group.
Holiday periods that can also be entered by date. All days in such periods will work according to the
settings in the holiday group, which is defined in the same way as the timer groups. (Note: for this
to work correctly the internal time, date and day need to be set correctly)
Floating setpoint: adjustment of setpoint according to ambient temperature
Free cooling: feature that allows the unit to be integrated into a free cooling application
Double evaporator pump: enables the use of two evaporator pumps (together or as a backup)
Lead-lag of compressors: the compressors can be set for lead-lag operation
Manual pump on: the facility to turn the pump on manually if the unit is off, in order to test
the pump operation
Time and date information: time, date and day can be set
Daily pump on: the facility to turn on the pump automatically each day at a set time to avoid
pump blockage as a result of its being idle for a long time
Changeable digital inputs/outputs: several digital inputs/outputs can be given a series of
functions depending on user preference.
Changeable digital inputs are: remote on/off, remote cooling/heating, dual setpoint and limit
capacity.
Changeable digital outputs are: heating mode/cooling mode output signal, 100% unit signal and
condenser pump (facility to steer condenser pump).
Temperature probe fine tuning: the facility to adjust the water temperature probes in order
to fine tune the measurement
Advanced freeze-up control: either normal freeze-up alarm can be used or the unit can be
allowed to go into freeze-up several times in a certain time period without generating an alarm,
the unit will only cease operating for a certain time.
Extended alarm history: up to 20 alarms can be reviewed
Languages: 5 languages can be selected on the controller (English, German, French, Italian,
Spanish)
pCO
2
controller