Daikin CDK25AZVMB [45/62] Euw16 24hz euw52 72hz euw32 48hz euw5 12hz

Daikin 4MX68AZVMB [45/62] Euw16 24hz euw52 72hz euw32 48hz euw5 12hz
44
SPECIFICATIONS
EUW32HZ EUW36HZ EUW40HZ EUW44HZ EUW48HZ
86 98 110 120 130
22.4 26.8 31.2 33.9 36.6
4
R-407C
hermetically sealed scroll
4/4 4/4 4/4 4/4 4/4
1,200x600x1,200
600 620 640 654 664
70 70 70 70 70
3N~/400V/50Hz
Nominal capacity kW
Nominal input kW
Capacity steps %
Refrigerant type
Compressor type
No. refrigerant circuits / compressors
Dimensions HxWxD mm
Machine weight kg
Sound power level dBA
Power supply W1
EUW5HZ EUW8HZ EUW10HZ EUW12HZ EUW16HZ EUW20HZ EUW24HZ
13.0 21.5 27.5 32.5 43 55 65
3.71 5.80 7.80 9.10 11.2 15.6 18.3
1 2
R-407C R-407C
hermetically sealed scroll hermetically sealed scroll
1/1 1/1 1/1 1/1 2/2 2/2 2/2
600x600x600 600x600x1,200
113 150 160 167 300 320 334
64 64 64 64 67 67 67
3N~/400V/50Hz 3N~/400V/50Hz
Nominal capacity kW
Nominal input kW
Capacity steps %
Refrigerant type
Compressor type
No. refrigerant circuits / compressors
Dimensions HxWxD mm
Machine weight kg
Sound power level dBA
Power supply W1
Nominal capacity kW
Nominal input kW
Capacity steps %
Refrigerant type
Compressor type
No. refrigerant circuits / compressors
Dimensions HxWxD mm
Machine weight kg
Sound power level dBA
Power supply W1
EUW52HZ EUW56HZ EUW60HZ EUW64HZ EUW68HZ EUW72HZ
141 153 165 175 185 195
38.0 42.4 46.8 49.5 52.2 54.9
6
R-407C
hermetically sealed scroll
6/6 6/6 6/6 6/6 6/6 6/6
1,800x600x1,200
920 940 960 974 988 1,002
72 72 72 72 72 72
3N~/400V/50Hz
option option description unit size availability
number 5 8 10 12 16 20 24 32 36 40 44 48 52 56 60 64 68 72
Not completely combinable options
zh glycol application chilled water temperature down to -5°C o o o o o o o o o o o o o o o o o o fact. mounted
zl glycol application chilled water temperature down to -10°C o o o o o o o o o o o o o o o o o o fact. mounted
Available kit
EKDME Evaporator hydronic connection double module - - - - - - - o o o o o - - - - - - kit
EKTME Evaporator hydronic connection triple module - - - - - - - - - - - - o o o o o o kit
EKDMC Condensor hydronic connection double module - - - - - - - o o o o o - - - - - - kit
EKTMC Condensor hydronic connection triple module - - - - - - - - - - - - o o o o o o kit
Impossible option combinations: o available
ZH + ZL - not available
OPTIONS
EUW16-24HZ EUW52-72HZEUW32-48HZEUW5-12HZ
00225•New products•01-12 09-11-2001 11:18 Pagina 45

Содержание

Скачать