Daikin LRMEQ5AY1 [38/156] K h h h k h h

Daikin LRLEQ8AY1 [38/156] K h h h k h h
SiENBE28-901 Field Settings
Air Cooled Refrigeration Condensing Unit 37
b-2. Setting mode 2 (for service)
c. Setting mode 3 (for servicing)
c. Setting mode 3 (for servicing)
Check when malfunction code “PJ” is displayed.
No.
Display of setting items
Display of setting conditions
Setting item H1P H2P H3P H4P H5P H6P H7P
4
INV compressor max. frequency
step control
khhhkhh
10
Setting of night-time compressor
frequency reduction
Set the start time with 2-8, set the
end time with 2-9.
khhkhkh
14
Correction of fan revolution
according to the high pressure
khhkkkh
19
Oil recovery continuous operation
time
khkhhkk
20
Speed change for cooling capacity
reduction
khkhkhh
27 INV compressor forced stop
khkkhkk
43 STD1 compressor forced stop
kkhkhkk
44 STD2 compressor forced stop
kkhkkhh
No.
Display of setting items
Display of setting conditions
Setting item H1P H2P H3P H4P H5P H6P H7P
3-21
Changing the compressor steps
during target oil recovery
kkhkkhh
No.
Display of setting items
Display of setting conditions
Setting item H1P H2P H3P H4P H5P H6P H7P
3-10 Capacity setting
khhkhkh
3-26 Setting the freezing and refrigeration
khkkhkh
3-39 Power supply voltage setting
kkhhkkk
(Factory set)
5A 6A 8A
10A 12A 15A 20A H1P H2P H3P H4P H5P H6P H7P
Compressor step control
15 21 34 39 42 58 62 khhhhhh
14 18 38 36 38 62 58 khhhhhk
13 17 42 42 36 57 khhhhkh
21 40 60 khhhhkk
16 36 56 khhhkhh
15 35 55 khhhkhk
14 34 54 khhhkkh
5A 6A 8A
10A 12A
15A 20A
H1P H2P H3P H4P H5P H6P H7P
Compressor steps (Factory set)
khhhhhh
Setting step: 1 Setting step: 2 khhhhhk
Setting step: 2 Setting step: 4 khhhhkh
Setting step: 3 Setting step: 6 khhhhkk
Setting step: 4 Setting step: 8 khhhkhh
Setting step: 5 Setting step: 10 khhhkhk
Setting step: 6 Setting step: 12 khhhkkh
H1P H2P H3P H4P H5P H6P H7P
High pressure correction = 0 (Factory set)
khhhhhk
High pressure correction = -0.2
khhhhkh
High pressure correction = 0.2
khhhkhh
High pressure correction = 0.4
khhkhhh
High pressure correction = 0.6
khkhhhh
H1P H2P H3P H4P H5P H6P H7P
40 min. (Factory set) khhhhhk
30 min. khhhhkh
20 min. khhhkhh
H1PH2PH3PH4PH5PH6PH7P
30 sec. (Factory set) khhhhhk
10 sec. khhhhkh
To reset the compressor after a forced stop, turn the power off
and back on again.
H1P H2P H3P H4P H5P H6P H7P
Normal control (Factory set)
khhhhhk
Inverter compressor forced stop
khhhhkh
To reset the compressor after a forced stop, turn the power off
and back on again.
H1PH2PH3PH4PH5PH6PH7P
Normal control (Factory set)
khhhhhk
STD1 compressor forced stop
khhhhkh
To reset the compressor after a forced stop, turn the power off
and back on again.
H1P H2P H3P H4P H5P H6P H7P
Normal control (Factory set)
khhhhhk
STD2 compressor forced stop
khhhhkh
5A, 6A
8A, 10A, 12A
15A, 20A
H1P H2P H3P H4P H5P H6P H7P
Compressor
frequency
13 27 34
khhhhhk
Factory set
17 31 42 khhhhkh
H1P H2P H3P H4P H5P H6P H7P
LRM(L)EQ5AY1 khhhhhk
LRM(L)EQ6AY1 khhhhkh
LRM(L)EQ8AY1 khhhhkk
LRM(L)EQ10AY1 khhhkhh
LRM(L)EQ12AY1 khhhkhk
LRM(L)EQ15AY1 khhhkkk
LRM(L)EQ20AY1 khhkhhh
H1P H2P H3P H4P H5P H6P H7P
Effective setting of Dip switches
khhhhhk
Freezing khhhhkh
Refrigeration khhhkhh
H1P H2P H3P H4P H5P H6P H7P
200V khhhhhk
400V khhhhkh