Oil trap is required no mater the outdoor unit is upper or lower than indoor unit, only when
Trap dimensions:
Setting method: install one oil trap for every 10 meters at the gas pipe.
Note: the drop between the oil trops should be 10m.
L
R
R
Gas pipe diameter Min. R (mm) L (mm)
15.88
40 80
19.05
40 80
25.4
40 80
31.8
60 90
38.1
60 100
the piping
drop is more than 10m.
Oil trap setting requirement:
Installation
-237-