Haier AC242ACEAA [392/408] Wired controller

Haier AU182AFERA [392/408] Wired controller
g Preset 
H Outdoor total capacity Actual value, decimal
In check mode, press [CHECK] to quit the check mode, and go into normal running
mode.
How to change the function switches?
new
type
old
type
function state of switch function description
Connected Set as simple controller D9 J02 Changeover of type of wired
controller
Cut off Set as standard controller
Connected Use the sensor in the wired
controller
D12 J06 Selection of room temp.
sensor
Cut off Use the sensor in the indoor
unit
Connected Common control D15 J07 Auto reset after power
failure
Cut off Auto reset after power failure
Connected Yes D14 J03 Display of room temperature
Cut off No
ON Set as slave controller SW
ķ
SW2
0ķ
Changeover of master or
slave controller
OFF Set as master controller
ON SW
ĸ
SW2
0ĸ
or ć
OFF ć
Connected Indoor unit in shorted time
function
JP8 D1 Shorten time function
Cut off Common control
Connected Send compulsorily defrost
signal to indoor unit
JP7 D2 Compulsorily defrost
Cut off Common control
Note:
The switches in grey can be operated after opening the cover of wired controller.
The old type: there are resistors of J03 and J06 beside the dip switch.
Wired controller
-375-