Haier 1UH071N1ERG [41/238] Smart power

Haier 1UH071N1ERG [41/238] Smart power
39
Smart Power
Item Model ADH125M1ERG/1UH125P1ERK
Function Cooling Heating
Capacity kW 12.5 (3.5~15.0) 13.7(4~18.0)
Sensible heat ratio 0.74 /
Total power input kW 3.67 (1.0~6.5) 3.91 (1.0~6.5)
Max. power input W 7000 7000
AEER or ACOP W/W 3.37 3.47
Dehumidifying capacity 10
-3
×m
3
/h 4.9
Power cable 4.0mm
2
Power source N, V, Hz 3, 380~415, 50/60
Running/Max. Running current A/A
6.1/10.8 6.5/10.8
Start current A 3
Circuit breaker A
3Ph40A (from outdoor
Indoor
unit
Unit model (color) ADH125M1ERG
Fan
Type×Number CENTRIFUGALX3
Speed (H-M-L) r/min 1200/1050/900
Fan motor input power/output power kW 0.32/0.4
Air-ow (H-M-L) m
3
/h 2250/1960/1680/1500
ESP Pa 30-120
Heat
exchanger
Type/Diameter mm Inner grooved pipe/φ7.0
Total area m
2
/
Dimension
External (L×W×H) mm×mm×mm 1500/700/250
Package (L×W×H) mm×mm×mm 1710/865/320
Drainage pipe (material, I.D./O.D.) mm PVC 26/32
Controller (O-Optional, S-Standard)
Wired YR-E17(S)/YR-E16A(O)
Infrared YR-HBS01 (O)
Fresh air hole dimension mm 125
Electricity heater kW /
Sound power noise level (H) dB (A) 62
Sound pressure noise level (H-M-L) dB (A) 39/36/33/31
Weight (Net / Shipping) kg / kg 52/62
Piping
Refrigerant
Type / Charge g R410A/3700
Recharge quantity g/m 45
Pipe
Liquid mm 9.52
Gas mm 15.88
Max.pipe lengh without
charge refrigerant
m 30
Between
I.D&O.D
MAX.Drop m 30
MAX.Piping length m 75
Connecting method Flared
Norminal condition:
Indoor temperature (cooling) : 27DB (°C)/19WB (°C) , Indoor temperature (heating) : 20DB (°C)
Outdoor temperature (cooling) : 35DB (°C)/24WB (°C) , Outdoor temperature (heating) : 7DB (°C)/6WB (°C)
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity
meter. It is a sound pressure noise level.