11.1 Select the Best Location
Install Monobloc unit at outdoor only.
Avoid location where ambient temperature is
below -20°C.
Must install on a flat horizontal and solid hard
surface.
A place where should not be any heat source or
steam near the Monobloc unit.
A place where air circulation is good.
A place where drainage can be easily done.
A place where Monobloc unit’s operation noise
will not cause discomfort to the user.
A place where accessible for maintenance.
Ensure to keep minimum distance of spaces as
illustrated below from wall, ceiling, or other
obstacles.
A place where flammable gas leaking might not
occur.
A place where the Monobloc unit’s piping and
wiring lengths come within reasonable ranges.
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
Do not place any obstacles which may cause a
short circuit of the discharged air.
Avoid install the Monobloc unit at a location where
suction side may be exposed directly to wind.
If Monobloc unit installed near sea, region with
high content of sulphur or oily location (e.g.
machinery oil, etc.), it lifespan maybe shorten.
When installing the product in a place
where it will be affected by typhoon or
strong wind such as wind blowing
between buildings, including the
rooftop of a building and a place
where there is no building in
surroundings, fix the product with an
overturn prevention wire, etc.
(Overturn prevention fitting model
number: K-KYZP15C)
When connecting solar pump station cable
between Monobloc unit and solar pump station,
the distance between both apparatuses shall be
2 ~ 8 meters and the length of the said cable must
be shorter than 10 meters.
Fail to do so may lead to abnormal operation to
the system.
11.2 Monobloc Unit Installation
Monobloc unit will become heavy when filled with
water.
Therefore, please install the Monobloc unit on strong
concrete floor, by considering weight of unit and water.
Fix Mono bloc unit on the concrete floor with M12
anchor bolt at 4 locations.
Pull-out strength of these anchor bolts must be
above 15000N.