Panasonic WH-MDF12C9E8 [43/125] Wire stripping and connecting requirement

Panasonic WH-MDF14C9E8 [43/125] Wire stripping and connecting requirement
43
5. Receiver shall be connected to “Room Thermostat”, refer to “Field Supply Accessories” table for details.
Receiver’s cable must be (4 or 3 x min 0.5 mm
2
), double insulation layer of PVC-sheathed or polychloroprene
sheathed cable. (connection refer to Diagram 4.2).
6. Tank OLP’s cable must be (2 x min 0.5 mm
2
), double insulation layer of PVCsheathed or polychloroprene
sheathed cable.
* note: if such connection deemed NO necessary for tank OLP, please connect jumper between terminal no
#13 and #14.
7. Tank Sensor shall be resistance type, please refer to Graph 4.1 for the characteristic and details of sensor. Its
cable shall be (2 x min 0.3 mm
2
), double insulation layer (with insulation strength of min 30V) of PVC-sheathed
or polychloroprene sheathed cable.
8. External Controller shall be connected to 1-pole switch with min 3.0mm contact gap. (connection refer to
Diagram 4.3). Its cable must be (2 x min 0.5 mm
2
), double insulation layer of PVC-sheathed or polychloroprene
sheathed cable.
* note: - When making such connection, kindly remove the jumper between terminal no #17 and #18.
- Switch used shall be CE compliance component.
- Maximum operating current shall be less than 3A
rms
.
9. Solar Three-way Valve’s cable shall be (3 x min 0.5 mm
2
), double insulation layer PVC-sheathed or
polychloroprene sheathed cable.
10. Must install Solar Connection PCB
to Monobloc unit when Solar Pump Station is utilized. Refer Solar
Connection PCB’s installation instruction for detail of installation.
11. Solar Pump Station’s cable shall be (2 x min 0.5 mm
2
), of double insulation PVC-sheathed or polychloroprene
sheathed cable. Strongly recommended install with maximum length of 10 meter only.
Terminal screw Tightening torque N•cm {kgf•cm}
M4 157~196 {16~20}
M5 196~245 {20~25}
11.4.1 Wire Stripping And Connecting Requirement
11.4.2 Connecting Requirement
For WH-MDF09C3E5:
The equipment’s power supply 1 complies with IEC/EN 61000-3-12 provided that the short-circuit power S
sc
is greater than or
equal to 858kW (for WH-MDF09C3E5) at the interface point between the user’s supply and the public system. It is the
responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply with a short-circuit power S
sc
greater than or equal to 858kW.