Panasonic WH-SDF16C9E8 [101/125] 1 indoor water outlet temperature sensor abnormality f45

Panasonic WH-SDF16C9E8 [101/125] 1 indoor water outlet temperature sensor abnormality f45
101
16.5.31 Indoor Water Outlet Temperature Sensor Abnormality (F45)
Malfunction Decision Conditions:
During startup and operation of cooling and heating, the temperatures detected by the indoor water outlet
temperature sensor are used to determine sensor errors.
Malfunction Caused:
1 Faulty connector connection.
2 Faulty sensor.
3 Faulty indoor unit PCB (main).
Abnormality Judgment:
Continue for 5 seconds.