12.5 Force Heater Mode Operation
The backup heater also serves as backup in case of malfunctioning of the outdoor unit.
1 Make sure the OFF/ON control panel LED is OFF (no operation).
2 Press the Force button to start the force heater mode operation.
3 During force heater mode, all other operations are not allowed.
4 Press OFF/ON button to stop the force heater mode operation.
12.6 Indoor Unit Safety
12.6.1 Indoor Unit Safety Control
1 When water pump is ON, the system will start checking flow switch status (ON/OFF).
2 If the flow switch ON for 10 seconds, the system will check on the water inlet temperature for 10 seconds.
If the water inlet temperature not exceeds 80°C, the water pump shall be continuously running with normal
mode.
If the water inlet temperature exceeds 80°C for continuously 10 seconds, the water pump will be OFF
immediately.
3 After water pump OFF for more than 10 minutes, it will be ON back and the indoor unit safety control
checking is restarted.
12.7 Auto Restart Control
1 When the power supply is cut off during the operation of Air-to-Water Heatpump, the compressor will re-
operate after power supply resumes.