i. Case 1
- THERMO OFF TEMP:
1. THERMO OFF TEMP = Heatpump tank target temperature + [+2°C].
2. Tank temperature > THERMO OFF TEMP for continuous 3 minutes, switch 3 ways valve to room side.
End Tank heat-up interval and start count heating heat-up interval.
- THERMO ON TEMP:
1. THERMO ON TEMP = Heatpump tank target temperature + [-3°C].
2. After Heating heat-up interval, always detect tank temperature. Switch to next tank heat-up interval
when tank temperature < THERMO ON TEMP
ii. Case 2
- Heatpump THERMO OFF TEMP:
1. Heatpump THERMO OFF TEMP = 55°C + [+2°C].
2. Water outlet temperature > Heatpump THERMO OFF TEMP for continuous 90 seconds, switch
3 ways valve to room side. End Tank heat-up interval and start count heating heat-up interval.
- THERMO ON TEMP:
1. THERMO ON TEMP = Tank temp. when heatpump thermo off + [-3°C].
2. After Heating heat-up interval, always detect tank temperature. Switch to next tank heat-up interval
when tank temperature < THERMO ON TEMP
iii. Case 3
- Heatpump THERMO OFF TEMP:
1. Water inlet temperature > 52°C for continuous 60 sec, switch 3 ways valve to room side. End tank
heat-up interval and start count heating heat-up interval.
- THERMO ON TEMP:
1. THERMO ON TEMP = Tank temp. when heatpump thermo off + [-3°C].
2. After Heating heat-up interval, always detect tank temperature. Switch to next tank heat-up interval
when tank temperature < THERMO ON TEMP
iv. Case 4: (Only during solar priority is set condition)
When solar pump ON, tank heat-up interval end early and 3 ways valve switch to room side.
- THERMO ON TEMP:
1. THERMO ON TEMP = Heatpump tank target temperature + [-3°C].
2. After Heating heat-up interval, always detect tank temperature. Switch to next tank heat-up interval
when tank temperature < THERMO ON TEMP and solar 3 way valve OFF.
3 Backup heater control:
o During heating heat up interval.
- Follow normal backup heater control operation.
o During tank heat-up interval.
- Backup heater OFF during this interval.
4 Booster heater control:
o During heating heat-up interval.
- Booster heater ON/OFF according to booster heater operation control.
o During tank heat-up interval.
- Once switch from heating heat-up interval to tank heat-up interval, turn off the booster heater and start
counting the BOOSTER HEATER DELAY TIMER.
- Booster heater turn ON after BOOSTER HEATER DELAY TIMER fufil and tank temperature lower
than tank set temperature.
- BOOSTER HEATER DELAY TIMER is clear when switch to heating heat-up interval.
5 Solar 3 way valve:
o Solar 3WV operates follow solar operation specification.
* Under solar priority is set condition, when solar 3WV is ON, booster heater turn OFF.