eco PDU Series User Manual
58
Rack Mounting
Before working on the rack, make sure that the stabilizers are secured to
the rack, extended to the floor, and that the full weight of the rack rests on
the floor. Install front and side stabilizers on a single rack or front
stabilizers for joined multiple racks before working on the rack.
Always load the rack from the bottom up, and load the heaviest item in the
rack first.
Make sure that the rack is level and stable before extending a device from
the rack.
Use caution when pressing the device rail release latches and sliding a
device into or out of a rack; the slide rails can pinch your fingers.
After a device is inserted into the rack, carefully extend the rail into a
locking position, and then slide the device into the rack.
Do not overload the AC supply branch circuit that provides power to the
rack. The total rack load should not exceed 80 percent of the branch circuit
rating.
Make sure that all equipment used on the rack — including power strips
and other electrical connectors — is properly grounded.
Ensure that proper airflow is provided to devices in the rack.
Ensure that the operating ambient temperature of the rack environment
does not exceed the maximum ambient temperature specified for the
equipment by the manufacturer
Do not step on or stand on any device when servicing other devices in a
rack.
The eco PDU’s Main Power Cord
Use the power cord supplied with this package. If it becomes necessary to
replace the cord supplied with this package, be sure to use a cord of at least the
same standard as the one provided.
Securing the Power Cables
To secure the cables in the eco PDU’s power outlets, use only the
ATEN Lock-Your-Plug cable holders that have been specifically
designed to work with the eco PDU. Using any other kind of cable securing
device could be highly dangerous. Please contact your ATEN dealer for
information about ATEN Lock-Your-Plugs.
Содержание
- User manual p.1
- Pe6216 pe6324 p.1
- Compliance statements p.2
- Pe device safety notice p.3
- User notice p.4
- User information p.4
- Telephone support p.4
- Online registration p.4
- Product information p.5
- Package contents p.5
- Introduction p.6
- Hardware setup p.6
- Contents p.6
- Chapter 3 p.6
- Chapter 2 p.6
- Chapter 1 p.6
- Basic operation and first time setup p.6
- Chapter 4 p.7
- Browser operation p.7
- Appendix p.7
- About this manual p.8
- This manual uses the following conventions p.9
- Conventions p.9
- This page intentionally left blank p.10
- Overview p.11
- Introduction p.11
- Chapter 1 p.11
- X iec 60320 c19 p.13
- Specifications page 62 p.13
- Pe6324g iec 60309 21 x iec 60320 c13 p.13
- Pe6324b nema l6 30p 24 21 x iec 60320 c13 p.13
- Pe6216g p.13
- Pe6216b 14 x iec 60320 c13 p.13
- Pe6216a iec 60320 c20 16 14 x nema 5 15r p.13
- Pdu yes p.13
- Note for the complete specifications of individual models please referto p.13
- Model inlet cord outlets p.13
- Comparison chart p.13
- Chapter 1 introduction p.13
- Bank yes p.13
- X nema 5 20r p.13
- Remote access p.14
- Power distribution p.14
- Operation p.14
- Features p.14
- Security p.15
- Management p.15
- Eco dc energy management web gui p.15
- Requirements p.16
- Sensors p.17
- Sensor management p.17
- Optional accessories p.17
- Cable holders p.17
- Pe6216a front view p.18
- Components p.18
- Note holes for aten lok u plug cable holders are located around the p.19
- Outlets see securing the cables page 19 for further information p.19
- Pe6216b pe6216g front view p.20
- Outlets see securing the cables page 19 for further information p.21
- Note holes for aten lok u plug cable holders are located around the p.21
- Pe6324b pe6324g front view p.22
- Outlets see securing the cables page 19 for further information p.23
- Note holes for aten lok u plug cable holders are located around the p.23
- Readout section p.24
- Rack mounting p.25
- Hardware setup p.25
- Chapter 2 p.25
- Before you begin p.25
- Pdu placement p.26
- For safety reasons the eco pdu should not be installed with the power sockets facing directly up or down and thus should only be installed with the power sockets facing out from a vertical position as shown below p.26
- Installation p.27
- Securing the cables p.29
- Securing the sensors p.30
- Operation methods p.31
- Eco dc p.31
- Chapter 3 p.31
- Browser p.31
- Basic operation and first time setup p.31
- First time setup p.32
- Network configuration p.33
- Moving on p.34
- Changing the administrator login p.34
- Logging in p.35
- Chapter 4 p.35
- Browser operation p.35
- The eco pdu main page p.36
- The web page screen components are described in the table below p.37
- Page components p.37
- Outlet access p.38
- Connections p.38
- Pdu status p.39
- Sidebar p.40
- Outlet status p.40
- This page lets you set up the power management configuration for the selected outlet the meanings of the field headings are given in the following table p.41
- The configuration page is used to configure the settings of the eco pdu at the individual power outlet level p.41
- Continues on next page p.41
- Configuration p.41
- When you have finished making your configuration settings click save p.42
- Continued from previous page p.42
- User management p.43
- Administrator information p.43
- Note values must be entered in both the name and password fields in p.44
- Key in a name and password in the name and password fields p.44
- Click save to save your settings p.44
- User information p.44
- To add a user do the following p.44
- The various options are explained in more detail in the following table p.44
- Set the outlet by outlet permissions of the user in the outlet field p.44
- Set the management field to enable p.44
- Select the user type in the management drop down menu p.44
- Order to enable an account p.44
- The system log event list p.45
- This page presents information about the selected device as described in the following sections p.46
- The device management page allows administrators and users with device management permission to configure and control overall eco pdu operations p.46
- General p.46
- Device management p.46
- Device configuration p.46
- Service ports p.47
- Ipv4 configuration p.48
- Event notification p.49
- Syslog server p.51
- Time zone p.52
- Date time p.52
- Network time p.53
- Manual input p.53
- Finishing up p.53
- Working mode p.54
- Security p.54
- Login failures p.54
- The account policy section governs policies in regard to usernames and passwords p.55
- Check a policy and enter the required information in the appropriate fields p.55
- Account policy p.55
- Login string ip filter mac filter p.56
- Adding filters p.57
- Ip filter mac filter conflict p.58
- Deleting filters p.58
- Modifying filters p.58
- Radius settings p.59
- Authentication authorization p.59
- Private certificate p.61
- Obtaining a ca signed ssl server certificate p.61
- Importing the private certificate p.61
- Generating a self signed certificate p.61
- When you click the maintenance tab the display opens with the firmware upgrade menu page which looks similar to the one below p.62
- The maintenance function is used to upgrade the eco pdu s firmware and to backup and restore the device s configuration settings p.62
- Maintenance p.62
- Firmware file p.62
- A description of the items shown in this panel are given in the table below p.62
- Restore p.64
- Backup restore p.64
- Backup p.64
- Appendix p.65
- Safety instructions p.65
- General p.65
- The eco pdu s main power cord p.68
- Securing the power cables p.68
- Rack mounting p.68
- Technical support p.69
- North america p.69
- International p.69
- Method 1 p.70
- Ip address determination p.70
- Method 3 p.71
- Method 2 p.71
- Specifications p.72
- Pe6216a p.72
- Eco pdu series user manual p.72
- Appendix p.73
- Pe6216b pe6324b p.73
- Pe6216g pe6324g p.74
- Eco pdu series user manual p.74
- Administrator login failure p.75
- Limited warranty p.76
Похожие устройства
-
Aten EC1000Краткое руководство по установке -
Aten EC1000Инструкция -
Aten EC1000Руководство пользователя -
Aten PE4104GРуководство пользователя -
Aten PE4104GКраткое руководство по установке -
Aten PE0112Краткое руководство по установке -
Aten PE0212Краткое руководство по установке -
Aten PE0110SКраткое руководство по установке -
Aten PE0209SКраткое руководство по установке -
Aten PE0210SКраткое руководство по установке -
Aten PE0324BКраткое руководство по установке -
Aten PE0316BКраткое руководство по установке