Midea MGRH16A-PA3Z [84/96] E6 malfunction dc fan motor malfunction

Midea MGRH16A-PA3Z [84/96] E6 malfunction dc fan motor malfunction
Aqua Mini Full DC Inverter Unitary Chiller 50Hz
84
E6 malfunction: DC fan motor malfunction
LED displays E6
Outdoor unit DC fan cannot work.
Refers to the wiring diagram to check whether
the unit wirin
g
is correct or not.
NO
Connect again.
YES
Check whether the power and voltage of the DC
fan motor is normal or not and whether the
voltage between red and black terminal of DC
motor is from 277V to 354V in waiting state.
YES
Check whether the power and voltage of the DC fan
motor is normal or not and whether the voltage between
white and black terminal of DC motor is from 15V in
waiting state.
NO
Replace IPM module.
Replace the main PCB.
YES
Whether the outdoor fan will work after the indoor fan
operates for 3 minutes.
NO
Check the voltage
between “+”,”-” port
of PFC module is within
277-354V.
Replace PFC
module board..
NO
NO
Check voltage
between yellow
and black
terminal of the
fan is over 2.4V
Replace fan.
YES
NO
YES
YES