413 Overmodulation function
(OVERMODULATION)
Value:
Off (OFF) [0]
On (ON) [1]
Function:
This parameter allows connection of the overmodula-
tion function for the output voltage.
Description of choice:
Off means that there is no overmodulation of the output
voltage, which means that torque ripple on the motor
shaft is avoided. This can be a good feature, e.g. on
grinding machines.
On means that an output voltage can be obtained
which is greater than the mains voltage (up to 5%).
414 Minimum feedback
(MIN. FEEDBACK)
Value:
-100,000,000 - FB
HIGH
(par. 415)
[-100000000 -]
0.000 [0]
Function:
Parameters 414 and 415 are used to scale the feed-
back range to physical values used by the user. The
setting will also be the bounds of the reference (pa-
rameters 204 and 205).
Used together with Process, closed loop mode (pa-
rameter 100).
Description of choice:
Is only active when parameter 203 has been set to
Min-Max [0].
415 Maximum feedback
(MAX. FEEDBACK)
Value:
(par. 414) FB
LOW
- 100,000,000
[- 100000000]
1.500.000 [1500000]
Function:
See description of parameter 414.
416 Reference/feedback unit
(REF/FEEDB. UNIT)
Value:
NO UNIT [0]
% [1]
PPM [2]
RPM [3]
bar [4]
CYCLE/min [5]
PULSE/s [6]
UNITS/s [7]
UNITS/min [8]
UNITS/h [9]
°C [10]
Pa [11]
l/s [12]
m
3
/s [13]
l/min [14]
m
3
/min [15]
l/h [16]
m
3
/h [17]
kg/s [18]
kg/min [19]
kg/h [20]
t/min [21]
t/h [22]
m [23]
Nm [24]
m/s [25]
m/min [26]
°F [27]
VLT
®
FCM Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.03.H6.02 - VLT
®
is a registered Danfoss trademark 61