Daikin EWAD495TZ-SSB2 [40/104] Ewad tz pr b

Daikin EWAD300TZ-SRB1 [40/104] Ewad tz pr b
EWAD~TZ-PR B
6"
6"
mm
Evaporatorwaterinlet/outlet
PIPING CONNECTIONS
2
2
No.
N.ofcircuits
94
86
kg
Refrigerantcharge
R134a
R134a
Refrigeranttype
REFRIGERANT CIRCUIT
69
68
dB(A)
SoundPressurelevel@1mdistance-
Cooling
90
90
dB(A)
SoundPower-Cooling***
SOUND LEVEL
2
2
No.
Quantity
20.0
20.0
l
Oilcharge
Inverter
DrivenSingle
Screw
Inverter
DrivenSingle
Screw
Type
COMPRESSOR
11.2
9.8
kW
Motorinput
700
700
rpm
Speed
16
14
No.
Quantity
57826
50423
l/s
Nominalairflow
800
800
mm
Diameter
BRS
BRS
Drive*
DPT
DPT
Type*
FAN
MCH
MCH
Type*
AIR HEAT EXCHANGER
CC
CC
Insulationmaterial*
33.2
26.2
kPa
Waterpressuredrop**
24.2
20.8
l/s
Waterflowrate
255
255
l
WaterVolume
S&T
S&T
Type*
WATER HEAT EXCHANGER
5532
5524
kg
OperatingWeight
5277
5269
kg
UnitWeight
WEIGHT
6783
6783
mm
Length
2258
2258
mm
Width
2483
2483
mm
Height
DIMENSIONS
GPSS
GPSS
Material*
IW
IW
Colour*
CASING
6.03
5.89
IPLV
5.63
5.41
ESEER
3.62
3.52
EER
139
123
kW
Unitpowerinput-Cooling
17
20
%
Capacitycontrol-Minimumcapacity
Stepless
Stepless
Capacitycontrol-Type
505
435
kW
Capacity-Cooling
COOLING PERFORMANCE
EWAD495TZ
-PR B2
EWAD420TZ
-PR B2
MODEL
All the perfrormances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient
35.0°C, unit at full load operation; operating f
luid: Water
; fouling factor = 0.
(*) IW: Ivory White; GPSS: Galvanized and Painted Steel Sheet; PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; CC:
Closed Cell; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter - BRS: Brushless
(**) The value referes to the pressur drop in the evaporator only.
(***) Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are mesuared in accordance with ISO 9614 and Eurovent 8/1
for Eurovent certified units. The certification refers only to the overall sound power level, the sound pressure is calculated from the sound power level and
are for information only and not cosidered binding. The minimum capacity indicated is referred to unit operating at standard Eurovent conditons.
Dimensions and weights are for indication only and not considered binding. Before desining the installation, consult the offical drawings available from the
factory at request. All the data are referred to standard unit without options. Data are subject to change without notice.
40/104
TECHNICAL SPECIFICATIONS