EWAD~TZ P-B- (PLATINUM SERIES)
Inordertooperatethefollowingoptionsmustbeincludedaccordingtothespecificoperatingarea:
Ref. 1: standard unit(nooptionsarerequiredtooperateinthisarea)
Ref. 2: standard unit opt. 08 (Brine) (chillermaynotunloadtominimumload)
Ref. 3: contact factory
Ref. 4: standard unit opt. 142 (HIGH AMBIENT KIT)
NOTE:
-Theabovegraphreferstotheunitoperatingatfullload.Unitmaybeabletooperateoutsidetheabove
envelopewithcompressorsunloading.Pleasecontactfactoryforfurtherdetails.
-ForoperationwithEWLTbelow4°C, theunitmustoperate withglycolmixture.The glycolpercentage
mustbeprovideaccordingtotheminimumELWTneeded.
- The above graphic representsa guideline about the operating limits of therange. Please refer to the
latestChillerSelectionSoftware(CSS)forrealoperatinglimitsworkingconditionsforeachsize.
-Inarea2and3chillermaynotunlloadtotheminimumload
67/104
OPERATING LIMITS