Daikin EWAD495TZ-SSB2 [42/104] Electrical specifications

Daikin EWAD190TZ-XLB1 [42/104] Electrical specifications
EWAD~TZ-SS B
INV
Startingmethod
225
A
Maximumrunningcurrent
10%
%
VoltagetoleranceMaximum
-10%
%
VoltagetoleranceMinimum
400
V
Voltage
3
No.
Phases
COMPRESSORS
36.4
A
Nominalrunningcurrentcooling
FANS
488
A
Maximumcurrentforwiressizing
486
A
Maximumrunningcurrent
414
A
Nominalrunningcurrentcooling
351
A
Maximumstartingcurrent
UNIT
10%
%
VoltagetoleranceMaximum
-10%
%
VoltagetoleranceMinimum
400
V
Voltage
50
Hz
Frequency
3
No.
Phases
POWER SUPPLY
EWAD700TZ
-SS B2
MODEL
Fluid: Water
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load.
In case of inverter driven units, no inrush current at start up is experienced.
Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current.
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.
The data are referred to the standard unit without options.
For the electrical data of the hydronic kit refer to "Options technical data"
All data are subject to change without notice. Plese refer to unit nameplate data.
42/104
ELECTRICAL SPECIFICATIONS