Daikin RXYQ10MAY1 [103/352] Stopping operation of slave units during master unit is in operation with multi outdoor unit system

Daikin RXYQ30MAY1 [103/352] Stopping operation of slave units during master unit is in operation with multi outdoor unit system
Special Control SiE39-407
92 Function
3.6.3 Stopping Operation of Slave Units During Master Unit is in Operation
With Multi-Outdoor-Unit System
While the master unit is in operation, this mode is used to set the refrigerant flow rate to a required level using a slave
unit in the stopped mode.
In cooling operation: The system operates in Mode A or Mode B listed in the table below.
In heating operation: The system operates in Mode A or Mode B listed in the table below.
The changeover operation for mode A and B is performed for the reason that the required refrigerant amount varies
depending on the indoor unit operation capacity.
Actuator Mode-A operation Mode-B operation
Compressor OFF OFF
Outdoor unit fan STEP4 OFF
Four way valve OFF Holds ON
Main motorized valve (EV1) 150 pls to 300 pls 0 pls
Subcooling motorized valve (EV2) 0 pls 0 pls
Hot gas bypass valve (SVP) ON ON
Receiver gas discharging valve
(SVG)
OFF OFF
Non-operating unit liquid pipe stop
valve (SVSL)
OFF ON
Mode transition conditions To Mode B when Tc
-
Tl >0.27×(Tc
-
Ta) +6
To Mode A when gas shortage signal
is sent from indoor unit
Ending conditions Slave units are required to operate.
Actuator Mode-A operation Mode-B operation
Compressor OFF OFF
Outdoor unit fan STEP2 STEP2
Four way valve ON ON
Main motorized valve (EV1) 0 pls 0 pls
Subcooling motorized valve (EV2) 0 pls 0 pls
Hot gas bypass valve (SVP) OFF OFF
Receiver gas discharging valve
(SVG)
OFF OFF
Non-operating unit liquid pipe stop
valve (SVSL)
OFF ON
Mode transition conditions
To Mode B when Tc
-
mean temperature of
indoor unit liquid pipes>10°C
To Mode A when motorized valve of
operating outdoor unit fully opens.
Ending conditions Slave units are required to operate.
Mode A or B operation
Mode A : Operating unit collects refrigerant.
Mode B : Stopping unit storage refrigerant.
Operating
unit
Stopping
unit