Test Operation 123
3.1.2 Wireless Remote Controller - Indoor Unit
BRC7C type
1. When in the normal mode, push the “ ” button for 4 seconds or more, and operation
then enters the “field set mode.”
2. Select the desired “mode No.” with the “ ” button.
3. Pushing the “ ” button, select the first code No.
4. Pushing the “ ” button, select the second code No.
5. Push the timer “ ” button and check the settings.
6. Push the “ ” button to return to the normal mode.
(Example)
When setting the filter sign time to “Filter Dirtiness-High” in all group unit setting, set the Mode
No. to “10”, Mode setting No. to “0” and setting position No. to “02”.
Mode no.
Field set mode
3
4
5
Second code no.
First code no.
2
(V2770)
1, 6