Daikin RXYQ10MAY1 [241/352] U3 check operation not executed

Daikin RXYQ46MAY1 [241/352] U3 check operation not executed
Troubleshooting by Indication on the Remote Controller SiE39-407
230 Troubleshooting
3.42 U3 Check Operation not executed
Remote
Controller
Display
U3
Applicable
Models
RXYQ5MA~48MA
Method of
Malfunction
Detection
Check operation is executed or not
Malfunction
Decision
Conditions
Malfunction is decided when the unit starts operation without check operation.
Supposed
Causes
Check operation is not executed.
Troubleshooting
(V3052)
Has the
check operation
performed on Outdoor
unit P.C.B?
Press the BS4 on P.C. board on
the master outdoor unit for 5
seconds or more to execute check
operation.
Replace the main P.C. board on
the outdoor unit.
NO
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.