Daikin EHFH03S18DJ3V — руководство по установке конфигурации системы отопления и охлаждения [113/204]

Превью страниц Страница 113 / 204
Daikin EHFH03S18DA3V [113/204] Quick wizard standard
9 | Configuration
Installer reference guide
113
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F
4P596806-1A – 2020.05
Confirm layout
Please confirm the system
layout. The system will
restart and will be ready for
first startup.
OK
Cancel
Confirm
Adjust
Result: The user interface reinitializes.
5 Proceed with the configuration of the system. When done, confirm the
configuration settings.
Result: The screen shortly turns OFF and Busy is displayed for several seconds.
9.2 Basic configuration
9.2.1 Quick wizard: Language / time and date
# Code Description
[A.1] N/A Language
[1] N/A Time and date
9.2.2 Quick wizard: Standard
Space heating/cooling settings
The system can heat up or cool down a space. Depending on the type of
application, the space heating/cooling settings must be made accordingly.
Space heating/cooling: Unit control method
# Code Description
[A.2.1.7] [C-07] Unit control method
0 (LWT control)
1 (Ext RT control)
2 (RT control)
LWT control:
Unit operation is decided based on the leaving water temperature regardless the
actual room temperature and/or heating or cooling demand of the room.
Ext RT control:
Unit operation is decided by the external thermostat or equivalent (e.g. heat pump
convector).
RT control:
Unit operation is decided based on the ambient temperature of the user interface.
Space heating/cooling: User interface location
# Code Description
[A.2.1.B] N/A User interface location
0 (At unit)
1 (In room)