Daikin EHFH03S18DA3V [148/204] Configuration
9 | Configuration
Installer reference guide
148
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F
4P596806-1A – 2020.05
# Code Description
N/A [5-08] Limit DI4
0A~50A, step 1A
kW limits for DI: Only applicable in case of power limitation mode based on
digital inputs and based on power values.
N/A [5-09] Limit DI1
0kW~20kW, step 0.5kW
N/A [5-0A] Limit DI2
0kW~20kW, step 0.5kW
N/A [5-0B] Limit DI3
0kW~20kW, step 0.5kW
N/A [5-0C] Limit DI4
0kW~20kW, step 0.5kW
Average timer
The average timer corrects the influence of ambient temperature variations. The
weather-dependent set point calculation is done on the average outdoor
temperature.
The outdoor temperature is averaged over the selected time period.
# Code Description
[A.6.4] [1-0A] Outdoor average timer:
0: No averaging
1: 12hours
2: 24hours
3: 48hours
4: 72hours
Ext. amb. sensor offset.
ONLY applicable in case of an external outdoor ambient sensor is connected and
configured.
You can calibrate the external outdoor ambient temperature sensor. It is possible
to give an offset to the thermistor value. The setting can be used to compensate
for situations where the external outdoor ambient sensor cannot be installed on
the ideal installation location (see installation).
# Code Description
[A.6.5] [2‑0B] Ext amb. sensor offset: Offset on the
ambient temperature sensor measured on the
external outdoor temperature sensor.
–5°C~5°C, step: 0.5°C
Disable protections
The software is equipped with an "installer-on-site" mode ([A.6.D]: Disable
protections) that disables automatic operation by the unit.