Daikin EHFH03S18DJ3V — руководство по установке и монтажу климатических систем [57/204]

Превью страниц Страница 57 / 204
Daikin EHFH03S18DJ3V [57/204] Unit installation
6 | Unit installation
Installer reference guide
57
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F
4P596806-1A – 2020.05
3 Place the switch box lower on the unit. Use the 2 hinges located lower on the
unit.
3
3
6.2.6 To close the indoor unit
1 Close the cover of the switch box.
2 Put the switch box back into place.
3 Reinstall the top panel.
4 Reinstall the side panels.
5 Reinstall the front panel.
6 Reinstall the upper front panel.
NOTICE
When closing the indoor unit cover, make sure that the tightening torque does NOT
exceed 4.1N•m.
6.3 Mounting the outdoor unit
6.3.1 About mounting the outdoor unit
When
You have to mount the outdoor and indoor unit before you can connect the
refrigerant and water piping.
Typical workflow
Mounting the outdoor unit typically consists of the following stages:
1 Providing the installation structure.
2 Installing the outdoor unit.
3 Providing drainage.
4 Preventing the unit from falling over.
5 Protecting the unit against snow and wind by installing a snow cover and baffle
plates. See "6.1Preparing the installation site"[448].