Daikin 2MXS40H2V1B [5/32] Specifications

Daikin 2MXS40H2V1B [5/32] Specifications
Split - Sky Air
®
• Outdoor Unit
3
Outdoor Unit • Multi model application • MXS-H
2 Specifications
2-1 Technical Specifications
2MXS40H2V1B 2MXS50H2V1B
Casing Colour Ivory white
Dimensions Unit Height mm 550
Width mm 765
Depth mm 285
Packed unit Height mm 612
Width mm 906
Depth mm 364
Weight Unit kg 38 42
Packed unit kg 43 47
Packing Weight kg 5
Heat exchanger Length mm 805 810
Rows Quantity 2
Fin pitch mm 1.5
Stages Quantity 24
Tube type ø7 Hi-XD ø8 Hi-XA
Fin Type WF fin
Treatment Anti-corrosion treatment
Fan Type Propeller fan
Air flow rate Cooling High m³/min 36 37
cfm 1,271 1,306
Nom. m³/min 33 34
cfm 1,165 1,200
Low m³/min 30 34
cfm 1,059 1,200
Heating High m³/min 32 34
cfm 1,130 1,200
Nom. m³/min 32 34
cfm 1,130 1,200
Low m³/min 32 34
cfm 1,130 1,200
Fan motor Model D50M-28
Output W 50
Speed Cooling High rpm 900 950
Nom. rpm 840 890
Low rpm 760 890
Heating High rpm 820 890
Nom. rpm 820 890
Low rpm 820 890
Sound power level Cooling Nom. dBA 62 63
Sound pressure level Cooling Nom. dBA 47 48
Heating Nom. dBA 48 50
Compressor Model 1YC23AGXD 2YC36BXD#C
Type Hermetically sealed swing compressor
Output W 600 1,100
Operation range Cooling Ambient Min. ºCDB 10
Max. ºCDB 46
Heating Ambient Min. ºCWB -15
Max. ºCWB 15.5
Refrigerant Type R-410A
Charge kg 1.20 1.60
Refrigerant oil Type FVC50K
Charged volume l 0.45 0.65